OPERATION
A/C and Heater
Explanations • Corrective action
Fault Code Read From the Heater
Malfunction description
31
Metering pump, Short circuit after +UB
Call the authorized service
No flame detected during operation cycle. • Check the fuel supply, the exhaust and the combustion air system. Call the authorized service if the problem is not solved
34
Safety time exceeded
4
Heater ignited during power stage (flame detected) and flame interruption signal issued. • Check the fuel amount, the blower speed, the fuel supply and the exhaust and the combustion air system. Call the authorized service if the problem is not solved Heater ignited during power stage (flame detected) and flame interruption signal issued. • Check the fuel amount, the blower speed, the fuel supply and the exhaust and the combustion air system. Call the authorized service if the problem is not solved Heater ignited during power stage (flame detected) and flame interruption signal issued. • Check the fuel amount, the blower speed, the fuel supply and the exhaust and the combustion air system. Call the authorized service if the problem is not solved Heater ignited during power stage (flame detected) and flame interruption signal issued. • Check the fuel amount, the blower speed, the fuel supply and the exhaust and the combustion air system. Call the authorized service if the problem is not solved
Flame interruption:
35
"POWER" control stage
Flame interruption:
36
"HIGH" control stage
Flame interruption during “Medium” control stage (D 8 W / D 10 W)
37
"Medium1" control stage (D 12 W)
Flame interruption:
38
"Medium 2" control stage (D 12 W)